| Penerangan Produk | |||
| Pensijilan standard | IEC60947-2 | ||
| Perkara No. | M7400 | ||
| Bilangan tiang | 3,.4 | ||
| Ciri-ciri elektrik mengikut IEC60947-2 dan EN60947-2 | |||
| Dinilai semasa Dalam | 250,300,315,350,400 | 450,500,550,600,630 | |
| Voltan Operasi Berkadar, Ue | AC:415V | AC:415V | |
| Voltan Tertebat Berkadar(Ui) | AC:800V | AC:800V | |
| Impuls terkadar menahan voltan, Uimpl | 8kV | 8kV | |
| Kapasiti pecah muktamad (kA rms Icu) | 220/240V | 75 | 75 |
| 380/400V | 50 | 50 | |
| 415V | 50 | 50 | |
| 550V | 20 | 20 | |
| Pemecahan perkhidmatan dinilai kapasiti (kA rms Icu) | 220/240V | 50 | 50 |
| 380/400V | 35 | 35 | |
| 415V | 35 | 35 | |
| 550V | 13 | 13 | |
| Fungsi perlindungan | Lebihan beban, litar pintas | Lebihan beban, litar pintas | |
| Jenis unit perjalanan | Termal-magnet | Termal-magnet | |
| Julat perjalanan magnetik | 400A | 400A | |
| Kategori penggunaan | A | A | |
| Ketahanan | mekanikal | 7000 operasi | 7000 operasi |
| Elektrik | 3000 operasi | 3000 operasi | |
| Sambungan | Sambungan hadapan | Sambungan hadapan | |
| Melekap | Standard | Membetulkan skru | Membetulkan skru |
| Dimensimm) | tiang | ||
| 3 | 257×140×145 | 257x140x145 | |
| 4 | 257×185×145 | 257×185×145 | |
Nota: Kedalaman mengikut saiz potongan pintu: cl untuk potongan besar, c2 untuk potongan kecil.
| A | A1 | B | B2 | F1 | F2 | F3 |
| 127.5 | 257 | 70 | 182 | 45 | 22.5 | 90 |